Bit addressing channel items
Details of operation principle: CAN_EDCP_Programmers_Guide.pdf
Control bits
- Control:5 - set emergency off
- Control:3 - set on
More information can be found in the document: CAN_EDCP_Programmers_Guide.pdf
Status bits
- Status:31 - is voltage rampspeed limit
- Status:30 - is fine adjustment
- Status:29 - is kill enable
- Status:28 - is init CRC check bad
- Status:27 - is internal communication bad
- Status:26 - is temperature bad
- Status:25 - reserved
- Status:24 - is max power
- Status:23 - is constant power
- Status:22 - is voltage bound lower is exceeded
- Status:21 - is voltage bound upper is exceeded
- Status:20 - is voltage ramp down is running
- Status:19 - is voltage ramp up is running
- Status:18 - is current ramp down is running
- Status:17 - is current ramp up is running
- Status:16 - is current ramp is running
- Status:15 - is voltage limit exceeded
- Status:14 - is current limit exceeded
- Status:13 - is trip exceeded
- Status:12 - is external inhibit
- Status:11 - is voltage bounds exceeded
- Status:10 - is current bounds exceeded
- Status:9 - is arc error
- Status:8 - is low current range
- Status:7 - is constant voltage
- Status:6 - is constant current
- Status:5 - is emergency off
- Status:4 - is ramp
- Status:3 - is high voltage on
- Status:2 - is input error
- Status:1 - is arc / is regulation error
- Status:0 - is positive polarity
More information can be found in the document: CAN_EDCP_Programmers_Guide.pdf
Event status bits
- EventStatus:31 - event voltage rampspeed limit
- EventStatus:30 - event set fine adjustment
- EventStatus:29 - event set kill enable
- EventStatus:28 - event init CRC check
- EventStatus:27 - event internal communication
- EventStatus:26 - event temperature not good
- EventStatus:25 - event voltage bottom
- EventStatus:24 - event max power
- EventStatus:23 - event constant power
- EventStatus:22 - event voltage bound lower
- EventStatus:21 - event voltage bound upper
- EventStatus:20 - event voltage ramp down
- EventStatus:19 - event voltage ramp up
- EventStatus:18 - event current ramp down
- EventStatus:17 - event current ramp up
- EventStatus:16 - event end of current ramp
- EventStatus:15 - event voltage limit exceeded
- EventStatus:14 - event current limit exceeded
- EventStatus:13 - event trip
- EventStatus:12 - event external inhibit
- EventStatus:11 - event voltage bounds exceeded
- EventStatus:10 - event current bounds exceeded
- EventStatus:9 - event arc error
- EventStatus:7 - event constant voltage
- EventStatus:6 - event constant current
- EventStatus:5 - event emergency off
- EventStatus:4 - event end of ramp
- EventStatus:3 - event on to off
- EventStatus:2 - event input error
- EventStatus:1 - event arc or event regulation error
- EventStatus:0 - reserved
More information can be found in the document: CAN_EDCP_Programmers_Guide.pdf
Event mask bits
- EventMask:31 - mask event voltage rampspeed limit
- EventMask:30 - mask event set fine adjustment
- EventMask:29 - mask event set kill enable
- EventMask:28 - mask event init CRC check
- EventMask:27 - mask event internal communication
- EventMask:26 - mask event temperature not good
- EventMask:25 - mask event voltage bottom
- EventMask:24 - mask event max power
- EventMask:23 - mask event constant power
- EventMask:22 - mask event voltage bound lower
- EventMask:21 - mask event voltage bound upper
- EventMask:20 - mask event voltage ramp down
- EventMask:19 - mask event voltage ramp up
- EventMask:18 - mask event current ramp down
- EventMask:17 - mask event current ramp up
- EventMask:16 - mask event end of current ramp
- EventMask:15 - mask event voltage limit exceeded
- EventMask:14 - mask event current limit exceeded
- EventMask:13 - mask event trip
- EventMask:12 - mask event external inhibit
- EventMask:11 - mask event voltage bounds exceeded
- EventMask:10 - mask event current bounds exceeded
- EventMask:9 - mask event arc error
- EventMask:7 - mask event constant voltage
- EventMask:6 - mask event constant current
- EventMask:5 - mask event emergency off
- EventMask:4 - mask event end of ramp
- EventMask:3 - mask event on to off
- EventMask:2 - mask event input error
- EventMask:1 - mask event arc or mask event regulation error
- EventMask:1 - reserved
More information can be found in the document: CAN_EDCP_Programmers_Guide.pdf